Leave Your Message

ACW series — Air-cooled box type water chiller

Industrial water chillers are divided into two types: air-cooled and water-cooled, mainly referring to the different condensers. Technically, water cooling is 300 to 500 kcal/h higher than air cooling; In terms of price, water cooling is much lower than air cooling; In the installation, water cooling needs to be incorporated into the cooling tower before use, and air cooling is mobile without other assistance. However, air cooled water chiller relies on the fan to dissipate heat, which has requirements for the ambient environment: such as ventilation, humidity, air PH value and etc...

    Scope of application

    • High speed motorized spindle of machining center
    • Water-cooled servo motor
    • CNC cutting machine
    • Quenching machine, high-power motor, high-power frequency converter
    • Semiconductor manufacturing, optical equipment and experimental instruments
    • Optical equipment, plastic machinery, mold, quenching machine and welding equipment
    • Food and plastics machinery, mould cooling

    Characteristics

    • Electrical elements refrigerating components are brands at abroad, thereby ensuring quality, safety and reliability
    • Multiple functions with perfect breakdown protection, passive alarm and remote control terminals
    • Compact structure and reliable performance
    • Delicate in appearance and durable in use
    • Easy to use, no special installation requirements, without the need for another cooling tower, water pump, water tank
    • Wide range of use: in order to meet the different requirements of freezing and cooling in varies industries, different series of compressors are used, and sophisticated process ensures stable work under extreme conditions.
    • Environmentally friendly refrigerant is available,such as R407c, R134a or R410a and so on.

    Specification

    Model

    ACW25PTA

    ACW50PTA

    ACW80PTA

    ACW120PTA

    ACW150PTA

    ACW180PTA

    ACW200PTA

    ACW250PTA

    ACW300PTA

    Cooling capacity(Kcal/h)

    2150

    4880

    8000

    12000

    15000

    18000

    20000

    24000

    30000

    Power Supply

    1Ø 220V/50Hz

    3Ø 380V/50Hz(customized)

    Input power(kW)

    1.36

    2.12

    3.4

    4.9

    6.8

    7.5

    8.5

    11.5

    12.8

    Rated current(A)

    5

    8

    6.1

    9.3

    11.6

    14.8

    16.8

    22

    25.6

    Compressor

    Input power(kW)

    0.89

    1.6

    2.6

    4.3

    5.2

    5.8

    7.8

    8.8

    10.4

    Operating current(A)

    3

    4.5

    4.6

    7.6

    9.8

    10.8

    14.2

    16.8

    20

    Quantity

    1

    1

    1

    1

    1

    1

    1

    2

    2

    Condenser

    Single power(kW)

    0.08

    0.1

    0.24

    0.24

    0.3

    0.45

    0.55

    0.55

    0.8

    Single current(A)

    1.2

    1.5

    0.48

    0.48

    0.6

    0.9

    1.1

    1.1

    1.6

    Quantity

    1

    1

    1

    2

    2

    2

    2

    2

    2

    Chilled water

    Flow(L/min)

    20

    25

    30

    41

    50

    63

    73

    85

    100

    Screw connection(Inch)

    G 1/2''

    G 3/4''

    G 1''

    G 1''

    G 1''

    G 1''

    G 1''

    G 1-1/4''

    G 1-1/4''

    Water pump

    Input power(kW)

    0.37

    0.37

    0.55

    0.75

    0.75

    0.75

    1.1

    1.1

    1.5

    Lift

    16

    16

    16

    20

    20

    22

    22

    25

    25

    Built-in water tank capacity(L)

    15

    38

    50

    75

    75

    100

    120

    200

    230

    Weight(Kg)

    65

    80

    120

    150

    170

    190

    220

    240

    320

    Remark:

    1.Cooling capacity is measured at water inlet temperature 12°C and water outlet temperature 7°C, suction air temperature 30°C and exhaust air temperature 35°C.

    2.The working ambient temperature should be less than 35°C.

    3.Scope of application: the temperature of chilled water tank is 5°C~35°C, the inlet and outlet temperature of chilled water are 3°C~10°C.

    4.Contact us for customized solutions.

    Model

    ACW400PTA

    ACW500PTA

    ACW600PTA

    ACW800PTA

    ACW1000PTA

    ACW1200PTA

    ACW1500PTA

    ACW2000PTA

    ACW2500PTA

    Cooling capacity(Kcal/h)

    40000

    50000

    60000

    80000

    100000

    120000

    150000

    200000

    250000

    Power Supply

    3Ø 380V/50Hz(customized)

    Input power(KW)

    18

    24.5

    26.5

    35.5

    37

    44.3

    61.9

    80.7

    95.7

    Rated current(A)

    36.8

    50.2

    53.2

    60

    67.7

    81.1

    113.3

    141.1

    167.8

    Compressor 

    Input power(kW)

    14.2

    18

    20.6

    28.4

    33.3

    35.76

    49.8

    66.6

    80.4

    Operating current(A)

    28.8

    66.2

    42.2

    56.8

    59.2

    63.7

    88.6

    118.4

    141

    Quantity

    1

    2

    2

    2

    2

    4

    4

    4

    4

    Condenser

    Single power(kW)

    0.95

    1.1

    1.1

    1.5

    2.2

    1.1

    1.1

    1.1

    1.3

    Single current(A)

    1.8

    2.2

    2.2

    3

    4.4

    2.2

    2.2

    2.2

    3

    Quantity

    2

    2

    2

    2

    2

    4

    6

    6

    8

    Chilled water 

    Flow(L/min)

    120

    200

    250

    250

    316

    374

    470

    632

    850

    Screw connection(Inch)

    G 1-1/2''

    G 1-1/2''

    G 2''

    G 2''

    DN65

    DN65

    DN80

    DN100

    DN100

    Water pump 

    Input power(KW)

    1.5

    2.2

    2.2

    3

    3

    4

    5.5

    7.5

    11

    Lift

    22

    22

    25

    20

    30

    31

    30

    25

    29

    Built-in water tank capacity(L)

    250

    300

    500

    550

    550

    600

    800

    1000

    1000

    Weight(Kg)

    900

    980

    1000

    1100

    1250

    1450

    1560

    2600

    3200

    Remark:

    1.Cooling capacity is measured at water inlet temperature 12°C and water outlet temperature 7°C, suction air temperature 30°C and exhaust air temperature 35°C.

    2.The working ambient temperature should be less than 35°C.

    3. Scope of application:the temperature of chilled water is 5°C~35°C, the inlet and outlet temperature of chilled water are 3°C~10°C.